Six Unpatched Danfoss Refrigeration Controller Flaws Could Allow Remote Takeover Without Login
Dutch security consultancy Midnight Blue has identified six unpatched vulnerabilities in Danfoss AK-SM800A refrigeration controllers that could allow a remote attacker to take over a device without logging in.
The vulnerabilities were discovered by Carlo Meijer of Midnight Blue, who found them during a manual review of the firmware in less than an hour. The flaws are in the web request handlers of the AK-SM800A, a device that runs a store's fridges and freezers and can be managed remotely by maintenance firms. Five of the flaws are in programs that run as root and do not require a login, allowing an attacker to execute code as root on older firmware versions.
The sixth flaw is in the gateway that enforces 'Strict mode,' a login protection that requires encrypted connections and session tokens. When the researchers ran firmware 5.3.2 in an emulator with Strict mode on, the flaw crashed the gateway. The crash could be turned into code execution with more work, and the gateway lacks basic exploit defenses such as stack canaries. With code running as root, an attacker could change the controller's settings, start defrost cycles, and hide that activity from its logs.
It's not really possible either because according to the file timestamp this firmware was likely built on October 29, before the second wave of cyber attacks and well before our vulnerability reports.
The researchers examined firmware version 5.3.2, then the newest, and say every version up to and including it is affected. The vendor lists software package 5.4.0, dated November, as its newest release for the AK-SM800A, but its readme and November update guide do not mention a fix for any vulnerability. The researchers found that the code almost certainly holds more flaws like these and call patching flaws one by one or turning on Strict mode 'a misallocation of scarce security and personnel resources.'
The controllers do not use secure boot, so an attacker could plant code that survives a factory reset and a firmware update. An attacker could also make a controller unusable until it is replaced. Government cybersecurity agencies in Belgium, Ireland and Germany told operators this week to take the controllers' management interfaces off the internet. The Belgian and Irish agencies said that for a controller left on the internet, updating the firmware, changing default passwords or turning on Strict mode is not enough on its own.
The attacks have already caused unwanted defrost cycles and destroyed stock in France starting October 11, and in a second wave across Europe that began last week. Germany's federal IT security agency, the BSI, says the AK-SM800A was involved in earlier incidents in which refrigeration units in several countries were tampered with. The agency has no information about any exploitation of the six new flaws, and neither other agencies nor researchers link the flaws to those incidents.
The German agency first said in a press release this week that 5.4.0 was not affected. Later the same day, it changed that in a corrected statement: it cannot rule out for now that 5.4.0 is affected. No CVE identifiers have been assigned, and the researchers are keeping technical details private while they work on disclosure with Danfoss. The vendor's advisory page lists no advisory for the six flaws as of today, and no date for a fix has been published.
Removing internet exposure must not wait for a patch, and it is needed even where firmware is current and Strict mode is on, the Centre for Cybersecurity Belgium says. The Belgian advisory and a similar Irish advisory recommend finding every controller whose management interface can be reached from the internet, including through a 4G or 5G modem, and removing that exposure. They also recommend giving remote access only through a secure VPN or a protected internal network, and allowing only a service company's IP addresses through a firewall as a short-term measure.
Operators should check temperature setpoints, defrost schedules, alarm settings, user accounts and remote-access settings for changes they did not make. The German agency adds that anyone who suspects a compromise should change all credentials and check that equipment connected to the controller works properly. Before cutting off the data a controller sends to its refrigeration service company, operators should check contract and insurance terms, the Belgian advisory says.
They should also set up protected remote access so that monitoring can continue. Ireland's National Cyber Security Centre also advises running the latest supported firmware, changing default passwords and turning on Strict mode, but says operators should not rely on those steps alone. Danfoss told Cooling Post on October 12 that most units hit in France were either older models that no longer receive updates or current AK-SM800A units running outdated firmware. The vendor fixed earlier flaws in the AK-SM800A in 2023 and 2025, including login bypass and command injection bugs.